Catalog No. Class ANSI Cantilever Strenght Tensile Strength  Torsional Strength Compression Strength  Net Weight
lbs kg lbs kg lbs kg lbs kg lbs kg
  TR 208 2.000 907.18 10.000 4535.92 8.000 3628.74 10.000 4535.92 27 12.25
  TR 210 1.000 453.602 12.000 5443.11 10.000 4535.92 15.000 6803.89 34 15.42
  TR 214 2.000 907.18 14.000 6350.29 12.000 5443.11 15.000 6803.89 50 22.68
  TR 216 1.500 680.39 16.000 7257.48 15.000 6803.89 25.000 11339.81 50 22.68
  TR 286 2.000 907.18 20.000 9071.85 60.000 27215.54 60.000 27215.54 143 64.86
  TR 288 1.450 657.71 20.000 9071.85 60.000 27215.54 60.000 27215.54 167 75.75
  TR 289 2.450 1111.30 25.000 11339.81 90,000 40823.31 90.000 40823.31 203 92.08
  TR 304 1.000 453.59 20.000 9071.85 60,000 27215.54 60.000 27215.54 270 122.47
  TR 312 1.000 453.59 20.000 9071.85 60,000 27215.54 60.000 27215.54 306 138.80
                       

 

Catalog No. Class ANSI Leakage Distance Critical Impulse  Withstand Voltage Radio Influence Voltage Data 
inch mm   Low Frequency Wet (kV) Impulse (kV) Test Volt. To ground / kV Max. RIV at 1000 kHz u V
  TR 208 24 609.6 170 60 150 15 100
  TR 210 37 939.8 225 80 200 22 100
  TR 214 43 1092.2 2580 100 250 30 200
  TR 216 72 1828.8 390 145 350 44 200
  TR 286 99 2514.6 610 230 550 73 200
  TR 288 116 2946.4 710 275 650 88 200
  TR 289 116 2946.4 710 275 650 88 200
  TR 304 165 4191 1.010 385 900 146 500
  TR 312 196 4978.4 1.210 455 1.050 146 500