ACWU90(-40c)XLPE 600 Volts 90c

SEARCH

ACWU

 

STANDARDS
National : CSA C22.2 N° 51
DESCRIPTION
CSA File #LL23462 Class 5811 01 - Cable
CSA File #LL19376 Class 5818 01 - Hazardous Location Cable

 

One to four compact ACM aluminum conductors with low temperature, sunlight resistant (black and colours) EXELENE® cross-linked polyethylene insulation (RW90 XLPE) and bare aluminum bonding wire in multi-conductor cables. Single conductor cables have aluminum concentric bonding wires. Conductor assembly is wrapped and enclosed in an interlocked aluminum armour with an overall low acid gas and low flame spread, sunlight resistant PVC jacket (LAG/LFS) with FT4 and AG14 rating. LEAD FREE and RoHS compliant.
8 and larger are HL rated for Class I Div 1 & 2 Groups A, B, C & D, Class II Div 1 & 2 Groups E, F & G and Class III Hazardous Locations.

 

APPLICATION
For exposed and concealed wiring in dry or wet locations and where exposed to the weather. Nexans cables are marked "SUN RES" for sunlight resistant.
For use in ventilated, non-ventilated and ladder type cable trays in wet and dry locations.
For direct earth burial (with protection as required by Inspection Authority).
For service entrance above or below ground.
For use in hazardous locations with approved connectors.
Minimum recommended installation temperature minus 40°C (with suitable handling procedures).
Maximum conductor temperature 90°C.

Rated 600 volts.

ACWU SINGLE STRANDED CONDUCTOR (PLUS BONDING WIRE)  
Size **   AWG or kcmil Insulation   Thickness Bonding Wire Size AWG or  kcmil Approximate Diameter Approximate     Net Cable     Weight  Ampacity*** (amps)   30°C   Ambient   
Armour PVC Jacket  
 
mm in mm in mm in kg/km lbs/kft  
 
4/0  1.4 0.055 2 24.99 0.984 27.59 1.086 779 538 300  
250 1.65 0.065 1 26.82 1.056 29.57 1.164 941 650 330  
300 1.65 0.065 1 28.14 1.108 28.6 1.216 1043 720 375  
350 1.65 0.065 1/0  29.21 1.15 31.45 1.238 1115 770 415  
400 1.65 0.065 1/0  30.42 1.198 31.4 1.306 1227 847 450  
500 1.65 0.065 2/0  31.3 1.263 34.8 1.37 1422 982 515  
600 2.03 0.08 2/0  35.05 1.38 36.7 1.488 1645 1136 585  
750 2.03 0.08 3/0  36.8 1.49 40.59 1.598 1961 1354 670  
1000 2.03 0.08 3/0  40.7 1.638 44.32 1.745 2392 1652 800  
                       
Insulation Colour Code:  Black (sunlight resistant)  
** Compact aluminum conductors are AA-8000 series aluminum alloy (ACM)  
***Ampacity in accordance with Table 3 of the Canadian Electrical Code.  
                       
ACWU THREE STRANDED CONDUCTOR (PLUS BONDING WIRE)  
Size **   AWG or kcmil Insulation   Thickness Bonding Wire Size AWG or  kcmil Approximate Diameter Approximate     Net Cable     Weight  Ampacity*** (amps)   30°C   Ambient   
Armour PVC Jacket  
 
mm in mm in mm in kg/km lbs/kft  
 
6 1.14 0.045 8 20.6 0.81 23.6 0.93 500 335 55#  
4 1.14 0.045 6 23.1 0.91 25.9 1.02 618 415 65  
3 1.14 0.045 6 24.4 0.96 27.2 1.07 673 452 75  
2 1.14 0.045 6 25.9 1.02 28.7 1.13 771 518 95#  
1 1.4 0.055 4 28.9 1.14 31.7 1.25 941 632 105  
1/0  1.4 0.055 4 31 1.22 33.5 1.32 1074 722 120  
2/0  1.4 0.055 4 33 1.3 35.8 1.41 1235 830 145  
3/0  1.4 0.055 4 35.8 1.41 38.3 1.51 1444 970 165  
4/0  1.4 0.055 4 38.6 1.52 41.9 1.65 1746 1173 185#  
250 1.65 0.065 2 42.2 1.66 45.5 1.79 2165 1455 215  
300 1.65 0.065 2 45.7 1.8 48.8 1.92 2661 1788 240  
350 1.65 0.065 2 48.3 1.9 51.6 2.03 2958 1989 260  
400 1.65 0.065 2 50.3 1.98 53.6 2.11 3234 2173 290  
500 1.65 0.065 1 54.9 2.16 58.2 2.29 3767 2531 330  
600 2.03 0.08 1 60.4 2.38 64.5 2.54 4561 3065 370  
750 2.03 0.08 1/0  65.7 2.59 72.6 2.86 5423 3644 405  
                       
Insulation Colour Code:  Black, Red, White (all sunlight resistant)  
**Compact aluminum conductors are AA-8000 series aluminum alloy (ACM)  
***Ampacity in accordance with Table 4 of the Canadian Electrical Code.  
# For 3-wire 120/240 V and 120/208 V service conductors for single dwellings, or for feeder   
conductors supplying single dwelling units of row housing, of apartments and similar   
buildings, and sized in accordance with Rules 8-200(1), 8-200(2) and 8-202(1), the   
allowable ampacity for sizes 6 AWG, 2 AWG and 4/0 AWG shall be 60 A, 100 A   
and 200 A respectively.  In this case the 5% adjustment Rule 8-106(1) cannot be applied.  
                       
ACWU FOUR STRANDED CONDUCTOR (PLUS BONDING WIRE)  
Size **   AWG or kcmil Insulation   Thickness Bonding Wire Size AWG or  kcmil Approximate Diameter Approximate     Net Cable     Weight  Ampacity*** (amps)   30°C   Ambient   
Armour PVC Jacket  
 
mm in mm in mm in kg/km lbs/kft  
 
6 1.14 0.045 8 22.6 0.89 25.6 1.01 583 392 55#  
4 1.14 0.045 6 25.4 1 28.7 1.13 774 520 65  
3 1.14 0.045 6 26.9 1.06 29.4 1.16 818 550 75  
2 1.14 0.045 6 28.7 1.13 31.2 1.23 932 626 95#  
1 1.4 0.055 4 32 1.26 34.8 1.37 1143 768 105  
1/0  1.4 0.055 4 34.3 1.35 36.8 1.45 1323 889 120  
2/0  1.4 0.055 4 36.6 1.44 39.1 1.54 1533 1030 145  
3/0  1.4 0.055 4 39.4 1.55 42.4 1.67 1839 1236 165  
4/0  1.4 0.055 4 42.4 1.67 45.7 1.8 2168 1457 185#  
250  1.65 0.065 2 47.2 1.86 50.5 1.99 2897 1947 215  
300  1.65 0.065 2 50.2 1.98 53.5 2.11 3289 2210 240  
350  1.65 0.065 2 53 2.09 56.3 2.22 3612 2427 260  
400  1.65 0.065 2 55.6 2.19 58.9 2.32 3966 2665 290  
500  1.65 0.065 1 60.4 2.38 64.5 2.54 4834 3248 330  
600  2.03 0.08 1 67 2.64 70.9 2.79 5725 3847 370  
750  2.03 0.08 1/0  72.9 2.87 76.7 3.02 6860 4610 405  
                       
Insulation Colour Code:  Black, Red, Blue, White (all sunlight resistant)  
**Compact aluminum conductors are AA-8000 series aluminum alloy (ACM)  
***Ampacity in accordance with Table 4 of the Canadian Electrical Code,   
assuming the fourth conductor is the neutral of a balanced 3 phase, 4 wire system.  
# For 3-wire 120/240 V and 120/208 V service conductors for single dwellings, or for feeder   
conductors supplying single dwelling units of row housing, of apartments and similar   
buildings, and sized in accordance with Rules 8-200(1), 8-200(2) and 8-202(1), the   
allowable ampacity for sizes 6 AWG, 2 AWG and  4/0 AWG shall be 60 A, 100 A   