Login

About

TRANSMISSION

DISTRIBUTION

SUBSTATION

TELECOM

Tools

AND MORE!!!

Airport Lighting Cables

SEARCH

AIRPORT 1

 

STANDARDS
National : CSA C22.2 N° 179
DESCRIPTION

Conductor: bare, annealed compressed copper conforming to ASTM B3 and Class B stranded in accordance with ASTM B8.

Conductor Shield: extruded semi-conducting cross-linked polyethylene.

Insulation: black cross-linked polyethylene.

 

Application

Suitable for installation in metallic and non-metallic conduits.
Suitable for direct burial underground.
Suitable for installation in accordance with Section 74 of the Canadian Electrical Code.
Temperature rating of 90°C dry or wet.
Termination and Splicing
For unshielded airport lighting cables, standard techniques and accessories may be used.

 

AIRPORT SERIES LIGHTING CABLE 5 KV NON-SHIELDED - CSA  
Conductor Size  ( AWG ) Conductor Shield  Thickness Insulation Thickness Nominal    Diameter Approximate Cable Weight   
 
mils mm mils mm inches mm lb / kft kg / km  
8 (7w) 15 0.38 110 2.8 0.404 10.27 99 147  
6 (7w) 15 0.38 110 2.8 0.437 11.11 134 200  
4 (7w) 15 0.38 110 2.8 0.483 12.28 190 283