Login

About

TRANSMISSION

DISTRIBUTION

SUBSTATION

TELECOM

Tools

AND MORE!!!

Instaglide T90 Nylon - TWN75 600Volts 90c

SEARCH

Instaglide T90 for catalogue

 

PVC Insulated Nylon Covered Cables
STANDARDS
National : CSA C22.2 N° 75
DESCRIPTION
CSA File #LL23462 Class 5832 02

U.L. Standard #83 - U.L. Approval # E70347

Single copper conductor with thin wall PVC insulation and nylon covering with FT1 rating. Rated 600 volts. LEAD FREE.

Nexans INSTAGLIDE® reduced friction construction in sizes 6 AWG and larger.

APPLICATION
General purpose building wire for installation as exposed or concealed wiring and in raceways (except cable trays) in dry or damp locations.
Minimum recommended installation temperature minus 10°C (with suitable handling procedures).
Maximum conductor temperature 90°C dry, 75°C in wet locations, and 60°C when exposed to oil.
Approved for use with ceiling fixtures.

Nexans INSTAGLIDE® reduced friction construction in sizes 6 AWG and larger.

Harmonized Product Print Legend:

E53058 F INSTAGLIDE® 2/0 AWG (67.4mm²) (UL) THHN OR THWN-2 OR GR II OR MTW 600 VOLT VW-1 CT USE MADE IN CANADA LL 23462 2/0 AWG CSA/ACNOR T90 / TWN75 NYLON FT1

 

INSTAGLIDE® T90 NYLON / TWN75  
Size AWG or
kcmil
Insulation  Thickness Nylon   Thickness  Approximate  Diameter Approx. Net  Cable Weight Ampacity  (amps at 30°C Ambient)  Where exposed to oil Conduit #  
 
Damp & Dry Wet  
 
mm in mm in mm in kg/km lbs/kft Free Air Conduit    # Free Air Conduit    #  
 
14 (1) 0.38 0.015 0.1 0.004 2.7 0.11 25 15 20 15 20 15 15  
12 (1) 0.38 0.015 0.1 0.004 3.1 0.12 35 23 25 20 25 20 20  
10 (1) 0.51 0.02 0.1 0.004 3.9 0.15 55 37 40 30 40 30 30  
   
14 (19) 0.38 0.015 0.1 0.004 2.8 0.11 24 16 20 15 20 15 15  
12 (19) 0.38 0.015 0.1 0.004 3.3 0.13 36 24 25 20 25 20 20  
10 (19) 0.51 0.02 0.1 0.004 4.2 0.17 58 39 40 30 40 30 30  
   
8 (19) 0.76 0.03 0.13 0.005 5.5 0.22 96 65 70 45 65 45 40  
6 (19) 0.76 0.03 0.13 0.005 6.5 0.26 146 98 100 65 95 65 55  
4 (19) 1.02 0.04 0.15 0.006 8.3 0.33 233 157 135 85 125 85 70  
   
3 (19) 1.02 0.04 0.15 0.006 9 0.36 288 193 155 105 145 100 80  
2 (19) 1.02 0.04 0.15 0.006 9.8 0.39 357 240 180 120 170 115 100  
1 (19) 1.27 0.05 0.18 0.007 10.9 0.43 446 300 210 140 195 130 110  
   
1/0 (19) 1.27 0.05 0.18 0.007 11.8 0.47 555 373 245 155 230 150 125  
2/0 (19) 1.27 0.05 0.18 0.007 12.9 0.51 698 470 285 185** 265 175 145  
3/0 (19) 1.27 0.05 0.18 0.007 14.2 0.56 862 579 330 210 310 200 165  
4/0 (19) 1.27 0.05 0.18 0.007 15.5 0.61 1077 724 385 235 360 230 195  
   
250 (37) 1.52 0.06 0.2 0.008 17.2 0.68 1272 855 425 265 405 255 215  
300 (37) 1.52 0.06 0.2 0.008 18.5 0.73 1521 1022 480 295 445 285 240  
350 (37) 1.52 0.06 0.2 0.008 19.7 0.78 1762 1184 530 325 505 310 260  
400 (37) 1.52 0.06 0.2 0.008 20.8 0.82 2002 1345 575 345 545 335 280  
500 (37) 1.52 0.06 0.2 0.008 22.9 0.9 2482 1668 660 395 620 380 320  
**For 3-wire 120/240 and 120/208V residential services or sub-services, the allowable ampacity   
for #2/0 AWG copper shall be 200 amperes. In these cases, the 5% adjustment per C.E. Code Rule 8-106(1)  cannot be applied.  
#Based on not more than 3 copper conductors in raceway or cable.