Product Description

Annealed solid or stranded uncoated copper conductor insulated with PVC, providing an abrasion, flame retardant, moisture and oil resistant insulation. Conductor is surface printed.

Colors available upon request.

Application

General purpose wiring for residential, commercial, and industrial lighting and power application as specified by the National Electric Code (NEC). Suitable for use in wet or dry locations where maximum continuous conductor temperatures do not exceed 60˚ C and for circuits not exceeding 600 volts.

Specification Data

Underwriters Laboratories Standard 83 for Thermoplastic Insulated Wires

Federal Specification J-C-30

National Electric Code Article 130

ASTM B-3 Soft or annealed copper wire
ASTM B-8 Concentric lay stranded copperconductors

 

Solid
Catalog
Number
Size (AWG) Stranding Insulation Thickness (Mils) Nominal Diameter  Weight  Ampacity* 3 Cond. In Conduit Ampacity* 1 Cond. In Free Air
(inches) (mm) lbs./1000ft Kg / Km
- 14 SOLID 30 0.125 3.18 18 26.78 15 20
- 12 SOLID 30 0.145 3.68 26 38.69 20 25
- 10 SOLID 30 0.165 4.19 40 59.52 30 40
- 8 SOLID 45 0.2185 5.55 64.5 95.98 40 60
- 6 SOLID 60 0.282 7.16 108 160.70 55 80

 

Stranded
Catalog
Number
Size (AWG) Stranding Insulation Thickness (mils.) Nominal Diameter  Weight  Ampacity* 3 Cond. In Conduit Ampacity* 1 Cond. In Free Air
(inches) (mm) lbs./1000ft Kg / Km
- 10 7 30 0.176 4.47 42 62.50 30 40
- 8 7 45 0.236 5.99 68 101.18 40 60
- 6 7 60 0.305 7.75 110 163.68 55 80
- 4 7 60 0.352 8.94 162 241.06 70 105
- 2 7 60 0.41 10.41 245 364.56 95 140