Triplexed XLPE-PVC Type USEI90 600Volts

SEARCH

TriplexedXLPEPVCTypeUSEI90600V cfl

 

Underground Distribution Cables
STANDARDS
National : CSA C22.2 N° 52
DESCRIPTION
Compact stranded AA-8000 series aluminum conductor material (ACM)

per ASTM B801 Class B or ASTM B836 (Single Input Wire), or aluminum

alloy 1350 per ASTM B400 Class B.
Black cross-linked polyethylene insulation
Colour-coded, flame retardant, sunlight resistant PVC jacket
Two phase conductors plus one full or reduced neutral conductor
CSA C22.2 No.52

 

TRIPLEXED USEI90  
Phase Conductor Size   (AWG/     Kcmil) Neutral Conductor Size   (AWG/  Kcmil) Insulation Thickness Jacket    Thickness Approximate              Diameter Linear Mass (Kg/Km)  
 
 
Phase  (mm) Neutral (mm) Phase  (mm) Neutral (mm) Phase  (mm) Neutral (mm) Overall (mm)  
 
 
4 4 1.1 1.1 0.8 0.8 9.45 9.45 20.4 330  
4 6 1.1 1.1 0.8 0.8 9.45 8.3 19.6 300  
2 2 1.1 1.1 0.8 0.8 10.9 10.9 23.5 460  
2 4 1.1 1.1 0.8 0.8 10.9 9.45 22.5 415  
1 1 1.4 1.4 1.1 1.1 13 13 28 640  
1 3 1.4 1.1 1.1 0.8 13 10.1 26.3 580  
1/0  1/0  1.4 1.4 1.1 1.1 14 14 30.2 760  
1/0  2 1.4 1.4 1.1 0.8 14 10.9 28.3 660  
2/0  2/0  1.4 1.4 1.1 1.1 15 15 32.3 900  
2/0  1 1.4 1.4 1.1 1.1 15 13 31 820  
3/0  3/0  1.4 1.4 1.1 1.1 16.2 16.2 34.9 1100  
3/0  1/0  1.4 1.4 1.1 1.1 16.2 14 33.5 870  
4/0  4/0  1.4 1.4 1.1 1.1 17.6 17.6 37.9 1320  
4/0  2/0  1.4 1.4 1.1 1.1 17.6 15 36.3 1180  
250 250 1.7 1.7 1.7 1.7 20.2 20.2 43.5 1660  
250 3/0  1.7 1.4 1.7 1.1 20.2 16.2 41.1 1420  
350 350 1.7 1.7 1.7 1.7 22.8 22.8 49.1 2200  
350 250 1.7 1.7 1.7 1.7 22.8 20.2 47.4 2000  
500 500 1.7 1.7 1.7 1.7 25.8 25.8 55.6 2950  
500 350 1.7 1.7 1.7 1.7 25.8 22.8 53.6 2650